BL932700-1 ORP Mini Controller with 4-20 mA Recorder Output, 115V +/- 1000 mV by Hanna Instruments

The BL 932700 is an ORP mini controller that has been designed for easy, affordable installation in tight spaces, ideal for simple yet effective process control. As a result of its compact size, the BL 932700 can be installed right next to tanks or vats.

This versatile controller is ideal for many applications, such as ORP monitoring bleaching processes, waste water treatment and swimming pools. BL 932700 permits automatic control of installations previously checked manually.

The instrument can be set for reducing or oxidizing dosage. It measures in the ±1000 mV range, with 1 mV resolution. Set point adjustment and calibration are simply performed through trimmers on the front panel. Users can choose automatic or manual dosing mode with a switch on the front panel. Manual control is particularly useful during maintenance operations, because it permits operators to enable or disable the dosing relay according to need.

The overtime control system advises users when the relay is active too long, helping to prevent over dosage. In addition, this model features a 4-20 mA analog output for recorder connection.

  • Easy to handle
  • Fire retardant casing
  • Selectable overdose protection system
  • Splash resistant cover

Order Information:

BL 932700-0 (12 VDC) and BL 932700-1 ( 115/230V) are supplied with mounting brackets, transparent cover and instruction manual.

Range ±1000 mV
Resolution 1 mV
Accuracy ±5 mV
Calibration manual, with CAL trimmer
Dosing Relay maximum 2A (fuse protected), 250 Vac, 30 VDC
Dosing Selection reducing or oxidizing, selectable on the back panel 
contact open=reductant dosage=relay ON if measure > set point
contact close
=oxidant dosage=relay ON if measure < set point
Setpoint adjustable from -1000 to 1000 mV
Overtime adjustable, typically from 5 to approx. 30 minutes
Recorder Output 4-20 mA, accuracy ±0.20 mA, 500 Ohm max load
Input Impedance 102 Ohm
Power Supply 1 = 115/230 Vac; 50/60 Hz Power Supply
Dimensions 79 x 49 x 95 mm (3.1 x 1.9 x 3.7’’)
Weight 300g (10.6 oz)