DL3 Data Logger by Fieldpiece

The DL3 Data Logger measures and records any parameter from any accessory head Instrument we offer. It holds up to 20,000 data points and can be set to record in a range from once every second to once every 999 hours. Record and export data in .xls format to your PC for use in work orders, troubleshooting and service contracts. A real-time clock time stamps every data point for pinpoint accuracy. Use multiple data loggers to monitor several parameters to make troubleshooting and commissioning easier. Combined with our accessory head instruments, we're comfortable saying the DL3 is the most versatile data logger for HVACR field service.

Designed exclusively for logging HVACR parameters the DL3 gives technicians an accurate, time stamped results in a compact design. Other features and benefits include:

  • TRIG (trigger) switch position. Set DL3 to record only the data you need.
  • Enhanced data scroll.
  • Bright, blue backlight.
  • Export data in .xls format.
  • Record data points manually, automatically, or trigger to log outside a range.
  • Real-time clock: second, minute, hour, day, month, year.
  • All data points are time stamped.
  • Multiple data sets of various parameters can be stored.
  • Easy downloading to a PC.
  • Cost-effective, multi-channel recording using multiple DL3 Data Loggers.
  • 20,000 data points.
  • Combine with the AAV3 Anemometer to easily determine CFM.
  • Works with all Accessory Heads

Includes

  • Expandable HVAC/R Data Logger - DL3
  • IR to USB Data Cord for DL2/DL3 - RCBLDL5
  • Fieldpiece Data Logger Software CD
  • 9-Volt Battery (installed)
  • Operator's Manual
General Specification
Display 4½ digit liquid crystal display (LCD) with a maximum reading of 19999.
Memory Up to 20,000 data points. Saved data is not lost when replacing battery.
Overrange "OL" mark indication.
Zero Automatic.
Operating environment 32°F to 122°F at <70% R.H.
Storage temperature -4°F to 140°F, 0 to 80% R.H. with battery removed.
Accuracy Stated accuracy at 73°F ±9°F, <75% relative humidity.
Temperature Coefficient 0.1 × (specified accuracy) per °F/°C. (32 to 64°F (0 to 17°C); 82 to 122°F (28 to 50°C)).
Power 6 single 1.5-volt AA batteries.
Battery life 1000 hours typical with alkaline.
Accessories One optical to USB pc cable, pc software CD, six 1.5V AA batteries (installed), and operating instr
Safety CE-EMC
DC volts
Ranges 200mV, 2000mV
Resolution 0.01mV
Accuracy ±(0.1% rdg + 3 dgt)
Input impedance 10MΩ
Overload protection 30VDC or 24VAC
AC volts (50Hz - 500Hz)
Ranges 200mV, 2000mV
Resolution 0.01mV
Accuracy ±(1.2% rdg + 10 dgts)
Input impedance 10MΩ
Overload protection 30VDC or 24VAC