73-0569RK-03 RI-413 Portable Halocarbon Indicator, Refrigerant Monitor with Loud Buzzer by RKI Instruments

The Model RI-413A utilizes non-dispersive infrared absorption (NDIR) technology as a convenient and inexpensive solution to the problem of measuring for halocarbon vapors like R-12, R-22, R-114, R-502, R404A, R-236FA and R-134A. By combining the versatility of a microprocessor and the selectivity of a non-dispersive infrared analyzer, RKI provides a compact and inexpensive halocarbon monitor for daily use in industrial safety and atmospheric control applications.

Each halocarbon is characterized by the amount of infrared energy the gas can absorb. Inside the Model RI-413A, a small pump continuously draws a sample of the atmosphere to be tested, through a length of hose and into an infrared chamber. The infrared ray is alternately transmitted through this chamber measuring the amount of energy passing through. As a result, the halogenated hydrocarbon vapor content is continuously monitored and digitally displayed directly in PPM units, to the nearest 25 ppm.

The microprocessor control provides easy to follow operational and malfunction instructions. Simple, reliable operation makes the RI-413A the smart choice for portable monitoring of halogenated hydrocarbon vapor levels.

Features

  • Digital display
  • Microprocessor controlled
  • Measurement of Instantaneous concentration for 7 kinds of halogenated hydrocarbon vapors
  • Measurement of average concentration over 1, 3 or 15 minutes
  • Adjustable alarm point from 0-full scale
  • Audible alarm
  • Illuminated display
  • Battery powered
  • Lightweight
  • Fully portable

Applications

  • Cold Storage
  • Cleaning Solvents
  • Air Conditioning
  • Shipboard use (Submarines)
  • Naval Ships
  • Degreasing

*Please note we can only ship RKI products to customers within the United States

Detection Principle Non-dispersive infrared absorption (NDIR)
Measurable Gas & Range R-12 (CC2F2) 0 – 4,975 ppm (25 ppm/digit)
R-22 (CHCIF2) 0 – 4,975 ppm (25 ppm/digit)
R-134a (CH2FCF2) 0–4,975 ppm (25 ppm/digit)
R-404A (C2H3F3)(C2HF5)(C2H2F4) 0 - 4,975 ppm (25 ppm/digit)
R-114 (CCIF2 -CCIF2) 0 – 2,475 ppm (25 ppm/digit)
R-502 (R115 + R22) 0 – 4,975 ppm (25 ppm/digit)
R-236FA (C3H2F6) 0 - 4,975 ppm (25 ppm/digit)
Notes: Reading on any one of these gases can be selected with the sensor switch on the top panel.
Other gases available as special versions. Consult factory.
Indication Method Continuous - Digital LCD display instantaneous concentration
Average - Digital LCD display of average concentration over 1, 3, or 15 minutes
Repeatability Less than ± 3% of full scale for R-12
Response Time Approx. 10 seconds to 90% indication
Sampling Method Motor-driven diaphragm pump
Alarms Audible for: Any user programed alarm point from 0 – full scale for any selected gas (short pulse)
End of averaging period (long tone)
Low battery (continuous tone)
Ambient Temperature & Humidity -10° C – +40°C, 10% – 95% RH (noncondensing)
Operating Hours Approx. 4 hours (based on use of alkaline dry cells at 25°C)
Recorder Output DC 0 – 100mV (linear)
Power Supply Alkaline battery, "D" size - 6 pcs. (Standard)
Ni-Cd rechargeable battery - 6 pcs (Optional)
115 VAC continuous operation adapter- (Optional)
Dimensions & Weight 230(W) x 190(H) x 113(D) mm, Approx. 2.6kg (instrument only) 5 1/2 lbs.