1-866-4 JJSTECH(1-866-455-7832)

Honeywell Analytics Floor Standing Cabinet with Rear Access 2000Hx800Wx600D includes Controller with HMI, PCBs, SD Card, with 100mm plinth, natural ventilation - TPPR-HF-R-LXXHPN

Item #:
TPPR-HF-R-LXXHPN
Brand:
Honeywell Analytics
$33,835.00
Qty
Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
Honeywell Analytics Floor Standing Cabinet with Rear Access 2000Hx800Wx600D includes Controller with HMI, PCBs, SD Card, with 100mm plinth, natural ventilation - TPPR-HF-R-LXXHPN

Honeywell Analytics Floor Standing Cabinet with Rear Access 2000Hx800Wx600D includes Controller with HMI, PCBs, SD Card, with 100mm plinth, natural ventilation...

$33,835.00

TPPR-HF-R-LXXHPN Floor Standing Cabinet with Rear Access 2000Hx800Wx600D includes Controller with HMI, PCBs, SD Card, with 100mm plinth, natural ventilation by Honeywell Analytics

Honeywell's Touchpoint Pro makes gas control system design, installation, configuration and operation simple. Touchpoint Pro uses a 'building block' approach, providing unrivalled flexibility. The building block approach employed by Touchpoint Pro delivers real value by being able to adapt to each unique system requirement. Ease of use and intuitive configuration ensures that installation, set-up and ongoing maintenance costs are reduced, providing a 'no compromise' solution designed to reduce the cost of on-site safety.

Flexible architecture

Touchpoint Pro has been designed to deliver flexibility, allowing the system to be freely configured to meet customers' varying needs. Touchpoint Pro's modularity means that any system topology can be built, including centralised, distributed I/Os, or a mix of both.

24/7 visibility of system status

Touchpoint Pro's central controller has a Webserver interface, which can be accessed when it is connected to a network, allowing users to remotely view status and event history, and acknowledge, reset or inhibit channels. This feature offers the possibility of system monitoring and data analysis from a remote location using multiple devices including tablets, smart phones and remote computers.

Simple installation and maintenance

Using a simple building block technique to create your system, Touchpoint Pro offers multiple features that simplifies installation, setup and ongoing maintenance. A key feature to this is the preloaded sensor catalogue, which contains a complete listing of all Honeywell Analytics' gas sensors, each with a full default configuration setting. A user can choose to configure input channel settings from the sensor catalogue, resulting in a quick and simple three step configuration process. The rest of the configuration will be loaded automatically.

Wide selection of inputs/outputs accepted

The Touchpoint Pro Input/Output plug-in modules can be combined up to a maximum of 16 input modules (64 channels) and 32 output modules (128 channels). Modules can be located in any Touchpoint Pro enclosure and power distribution is via the communication/power Rail. Touchpoint Pro accepts analogue, digital and relay modules making it one of the most flexible controllers available.

Intuitive user interface

The heart of the Touchpoint Pro is the central controller, which includes the user interface. The user interface features a full colour LCD touch screen, and provides engineers with an intuitive solution to system set-up and deployment. Easily accessible icons, supported by drop-down menus ensure that even the most complex of system configurations can be commissioned with efficiency.

Aside from ease of use, Touchpoint Pro's user interface also includes some valuable aspects that help engineers save time, whilst setting up and commissioning a system.

Features & Benefits

  • Webserver ensures 24/7 system status visibility for constant safety
  • Flexible system architecture to meet specific site needs
  • Easily accessible system status that can be seen at a glance

Quick Specs

  • Up to 64 channels of detection and 128 output channels
  • Digital and analogue inputs available
  • Mulitple mounting possibilities
  • Touchscreen user interface
ENCLOSURE
WALL MOUNT CONTROLLER ENCLOSURE
Dimensions (H x W x D)
600 mm x 600 mm x 300 mm (Mild Steel)
800 mm x 600 mm x 300 mm (Mild Steel)
1200 mm x 600 mm x 300 mm (Mild Steel)
WALL MOUNT REMOTE UNIT ENCLOSURE
Dimensions (H x W x D)
600 mm x 600 mm x 300 mm (Mild Steel)
800 mm x 600 mm x 300 mm (Mild Steel)
19" 5U RACK UNIT
Dimensions (H x W x D)
483 mm x 222 mm x 110 mm (Mild Steel)
FLOOR STANDING CABINETS (FRONT OR REAR ACCESS)
Dimensions (H x W x D)
2000 mm x 800 mm x 600 mm (Mild Steel)
CONTROL MODULE AND USER INTERFACE
LCD Touch Screen
5.7" TFT Colour LCD with LED
Backlight (resistive touch screen)
320 x 240 pixels (QVGA) Resolution
Active area 115.2 mm(H) x 86.4 mm(V)
Front Panel Dimension
483 mm x 222 mm
Operating Temperature
-20°C to +55°C
Storage Temperature
-20°C to +55°C
Operating Humidity
10% to 90% RH (non-condensing)
INPUT SUPPLY
Input Voltage
18-32 Vdc (24 Vdc nominal)
Voltage Ripple
50 mVp-p (maximum)
CONTROLS AND INDICATORS
Front Panel LED
Green Power LED
Red Alarm LED
Yellow Fault LED
Yellow Inhibit LED
Front Panel Buttons
Alarm Accept Push Button, Alarm Reset
Push Button; Alarm Buzzer
Relay Outputs
2 System State Relays
Redundancy
Redundant Control Centre Board (CCB)
Ring Network
EXTERNAL COMMUNICATION
Interfaces
Redundant RS485 Modbus
RTU interface
Ethernet
INPUT/ OUTPUT MODULES
COMMON SPECIFICATIONS
Dimensions (H x W x D)
35.0 mm x 99.5 mm x 114.5 mm
Power Supply
18-32 Vdc (24 Vdc nominal)
DIN rail compatibility
TS-35 / 15
Operating Temperature Range
-40°C to 55°C
Operating Humidity Range
10 to 90% RH (non-condensing)
Inputs
Up to 16 Input Modules (64 Input channels) per system Analogue Input Module 4-20 mA; 4-channels for 2 or 3 wire 20 mA detector signals Analogue Input Module mV-Bridge; 4-channels for mV-Bridge signals Digital Input Module; 4-channels for switched input devices
Outputs
Up to 32 Output Modules (128 Output channels) per system Relay Output Module; 4-channels incorporating 4 single pole change over (SPCO) relays; Analog Output Module 4-20 mA
COMMUNICATION / POWER RAIL
Description
5, 7, 9, or 10-way Communication / Power Rail consists of 1 DIN Rail, 1 Ring Coupling Module (RCM) and 5, 7, 9, or 10-way backplanes
Power Supply
Operating voltage range - 18 Vdc to 32 Vdc (double-check)
Power Supply mounted on Din-Rail
120 W 24 Vdc, 240 W 24 Vdc, 480 W 24 Vdc, Power Supply Redundancy Module (RDN Module), Uninterruptible Power Supply Module (UPS)
BACK-UP BATTERY
Description
24 V sealed lead acid battery, 12 Ah or 27 Ah options
Electrical Connection
2 x 12 Vdc batteries in series
Dimensions (H x W x D)
300 mm x 395 mm x 215 mm
Weight
12 Ah version: 15.7 kg
27 Ah version: 25 kg
APPROVALS
Compliance
Compliance with EMC/RFI (EN 50270:2006) and LVD (EN 61010-1:2010) CSA-C22.2 No. 61010-1-04, UL Std. No. 61010-1 (2nd Edition)
Advanced requirements
ATEX Performance Approvals - EN 50271:2010; EN 60079-29-1; EN 45544-1 /-2 /-3; EN 50104:2010 C22.2 No. 152-M1984, FM Std. 6310 and 6320
Highest level of safety
IEC/EN 61508 and EN 50402 SIL2 certification

Questions & Answers