1-866-4 JJSTECH(1-866-455-7832)

Honeywell Analytics 301IRF Refrigerant Gas Sensor - S301-IRF-R448A

Item #:
S301-IRF-R448A
Brand:
Honeywell Analytics
Honeywell Analytics 301IRF Refrigerant Gas Sensor - S301-IRF-R448A
$2,002.00
Qty
Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
Honeywell Analytics 301IRF Refrigerant Gas Sensor - S301-IRF-R448A

Honeywell Analytics 301IRF Refrigerant Gas Sensor - S301-IRF-R448A

$2,002.00

S301-IRF-R448A 301IRF Refrigerant Gas Sensor by Honeywell Analytics

Install Honeywell 301IRF sensor at low levels in chiller room for reliable detection of a variety of refrigerant gasses. Requires installation with a 301EM-20 controller.

Product Overview:

Discreet design and rugged ABS-Polycarbonate housing for the 301IRFS set the standard for "at the source" gas detection in a chiller room. Mount directly to the chiller pad or low on the wall in close proximity to achieve early notifications in the event of a refrigerant leak.

ASHRAE No 15-2001 Mechanical Standard and B-52 Code Compliance. The ASHRAE and B-52 security standards have been established to minimize risk and protect the safety of mechanical room personnel and the environment at large. Honeywell's 301IRF, together with the 301EM mechanical room controller, provides a complete solution that meets and even exceeds these rigorous standards. The 301EM can be configured to offer automatic fan, horn and strobe activation in addition to manual fan activation when the 301IRF detects a refrigerant.

User Friendly:

  • State-of-the-art infrared sensor technology
  • LED indicator
  • Low-profile and rugged construction for low mounting in chiller/mechanical room

Economical Solution:

  • Cost-effective answer for installation in areas where refrigeration gas hazards may be present

Detectable Gasses:

  • R11, R22, R123, R125, R134A, R404A, R407C, R410A, R448A, R449A, R507A, R513A, R514A, R4310, 1233ZD, 1234ZE.

Features & Benefits:

  • Infrared sensing technology responds promptly
  • Low-profile design suited for mounting directly to chiller pad or low on nearby wall
  • Low maintenance

Quick Specs:

  • Power requirement operates on 12 VDC power only
  • Dimensions 4" H x 11" W x 2.5" D (10.2 x 28 x 6.3 m)
  • Weight 2.33 lbs (0.603 kg)
General Specification
Use Infrared refrigerant sensor to be used with the 301EM-20
Gases Detected R11, R22, R123, R125, R134A, R404A, R407C, R410A, R448A, R449A, R507A, R513A, R514A, R4310, 1233ZD, 1234ZE
Sensing Technology Infrared sensor
Measurement Range 0-1,000 ppm
Resolution 1 ppm
Deadband 20 ppm
Accuracy ± 40 ppm @ 500 ppm
Response Time (T90) 60 seconds
Warmup time 15 minutes
Operating Environment Indoor Use
Operating Temperature Range 32° to 100°F (0° to 40°C)
Operating Humidity Range 0 to 95% RH (non-condensing)
Enclosure ABS – Polycarbonate
Size 4 (H) x 11 (W) x 2.5 (D) in. (10.2 x 28 x 6.3 cm)
Weight 2.33 lbs. (0.603 kg)
Visual Indicators Normal Operation: LED blinks according to the sensor addresses on the 301EM-20
Failure Indication: LED will remain on