PID Case Study

Case Study

  • Fuel barge explosion and cleanup
  • On February 21, 2003, a fuel barge loaded with gasoline exploded at a fuel loading dock on Staten Island, New York
  • Two workers were killed and another critically burned
  • The explosion was the result of an accident, not terrorism or sabotage
  • The barge had unloaded about half its cargo of 4 million gallons of unleaded gasoline when the explosion occurred
Case Study
Case Study

As the blaze was at its height, officials used tugs to push a nearby barge loaded with 8 million gallons of gasoline to the other side of the waterway, where they covered it with water and foam to ensure that it did not explode.

Case Study
Case Study

USCG photo by PA3 Mike Hvozda

  • Once the fire was extinguished and the barges cooled, Marine Chemist and Coast Guard personnel conducted structural inspections
  • Exposure to toxic VOCs was a primary concern
  • Chemicals of concern included the remaining gasoline, benzene, total BTEX (benzene, toluene, ethylbenzene, and xylenes) and total polycyclic aromatic hydrocarbons (such as naphthalene)

Actual toxicity testing results from gasoline fuel barge #1

Previous Loadings: Cat Feedstock/Crude Oil/Cat Feedstock

SPACE % LELPPM TVOC (iso)PPM Benzene%TVOC from benzene
No (1) Port Cargo Tank 032.80.82.44%
No (2) Port Cargo Tank 038.20.41.05%
No (3) Port Cargo Tank 045.50.40.88%
No (4) Port Cargo Tank 075.80.30.4%
No (5) Port Cargo Tank 064.30.30.47%
No (1) Stbd Cargo Tank 034.80.61.72%
No (2) Stbd Cargo Tank 044.60.30.67%
No (3) Stbd Cargo Tank 039.60.20.51%
No (4) Stbd Cargo Tank 058.40.40.68%
No (5) Stbd Cargo Tank 064.80.50.77%

TVOC alarm setting based on fractional concentration benzene for Barge #1

Worst case (No 1 Port Cargo Tank)

TVOC hazardous condition threshold alarm of 172 ppm isobutylene would prevent exceeding the PEL for benzene of 1.0 PPM

41 x .0244 = 1.0004 ppm

TVOC Hazardous Condition Threshold Alarm for compliance with:

Benzene Exposure Limit 1.0 PPM0.5 PPM0.1 PPM
TVOC alarm setting 41 PPM20.5 PPM4.1 PPM

Actual toxicity testing results from gasoline fuel barge #2

Previous Loadings: Natural Gasoline (3X)

SPACE % LELPPM TVOC (iso)PPM Benzene%TVOC from benzene
No (1) Port Cargo Tank 037.30.00%
No (2) Port Cargo Tank 044.10.10.23%
No (3) Port Cargo Tank 053.80.20.37%
No (4) Port Cargo Tank 048.20.10.21%
No (5) Port Cargo Tank 068.50.40.58%
No (1) Stbd Cargo Tank 013.20.00%
No (2) Stbd Cargo Tank 029.00.00%
No (3) Stbd Cargo Tank 058.10.10.17%
No (4) Stbd Cargo Tank 048.70.20.41%
No (5) Stbd Cargo Tank 063.30.30.44%

TVOC alarm setting based on fractional concentration benzene for Barge #2

Worst case (No 5 Port Cargo Tank)

TVOC hazardous condition threshold alarm of 172 ppm isobutylene would prevent exceeding the PEL for benzene of 1.0 PPM

172 x .0058 = 0.9976 ppm

TVOC Hazardous Condition Threshold Alarm for compliance with:

Benzene Exposure Limit 1.0 PPM0.5 PPM0.1 PPM
TVOC alarm setting 172 PPM86 PPM17.2 PPM