Bacharach 6400-0035 MGS-250 Infrared R452A Replacement Detector

Bacharach 6400-0035 MGS-250 Infrared R452A Replacement Detector

$1,527.50

6400-0035 MGS-250 Infrared R452A Replacement Detector by Bacharach

Bacharach's new MGS-250 Infrared Refrigerant Gas Transmitter is the leader in performance and flexibility at an economical price. There are two versions available - a cost-effective broadband sensor used for gross leak detection or gas-particular versions that are even more distinct, pre-calibrated and characterized for response to specific refrigerants. Its simple-to-use interface gives the user the ability to set all parameters and outputs without opening the unit, moving jumpers, using mulitmeters or adjusting potentiometers.

The MGS-250 family is a cost effective solution for detecting a variety of refrigerants without the limitations posed by solid-state sensor technologies. The long-life, proprietary NDIR infrared sensor allows for accurate low-level leak detection (0-3,500 ppm), delivering up to 5-7 years of maintenance-free operation without the need for costly annual gas calibrations. Infrared sensing technology makes the MGS-250 immune to cross sensitivities to combustible and toxic gas as well as changes in temperature and humidity. The unit has an alpha-numeric LED display to show constant real-time readings, an on-board LED indicator for when the sensor is in an alarm state, and an audible alarm to alert personnel in the area that levels have exceeded the desired limit. An optional protective splash guard is available for use in areas with high water spray such as food and beverage facilities or chiller rooms.

Features & Benefits:

  • Long-life, Non-Dispersive Infrared (NDIR) sensor allows for accurate low-level leak detection
  • Detects all refrigerants (CFC, HFCs, HCFC, HFO's), including HFO1234YF, HFO1234ZE, R410a & R22
  • Fast-responding, refrigerant-specific sensor with no cross interferences to other gases
  • No field calibrations required
  • Modbus RTU interface to connect to BAS/BMS systems and on-board alarm relay
  • User selectable analog output: 4-20 mA, 0-5V, 1-5V, 0-10V, 2-10V
  • Bright, alpha-numeric LED real-time display with on-board audible and visual alarms
Power Supply 24 VDC @ 0.15 A min;
24 VAC, 5 VA min @ 50/60 Hz, 2.5 W max
Power Monitoring Green LED
Visual Alarm Red 4-digit LED display
Audible Alarm Buzzer (audible alarm), enable/disable
Fault Monitoring Fault codes presented to user
Analog Outputs 4-20 mA; 0-5 V; 0-10 V; 1-5 V; 2-10 V
Relay 1 relay rated 1 A @ 24 VAC/VDC (0.5A, 125V AC UL rating)
Range 0-3500 ppm
Squelch1 Readings below 75 ppm are squelched by default
Communication: Modbus RTU over RS-485 Baud rate: 9,600 or 19,200 (selectable)
Start bits: 1; Data bits: 8
Parity: None, odd, even (programmable)
Stop bits: 1 or 2, programmable
Retry time: 500 ms (min time between retries)
End of msg: Silent 3.5 characters
Alarm Delay Selectable; 0 to 15 minutes
IP Rating Not IP rated. An accessory splash shield is available for areas requiring additional protection from wash down.
Response Time T90 < 5 minutes
Temperature Rating -22° to 104° F (-30° to 40° C)
Humidity and Elevation 5-90% relative humidity, non-condensing,
0-10,000 ft. altitude
Weights/Dimensions 6.3 oz, 4.0" x 5.5" x 1.5" (180 g, 102 x 140 x 37 mm)
Enclosure ABS plastic; UL flammability rating of 94V-0
Approvals CE, UL/CSA/IEC/EN 61010-1