1-866-4 JJSTECH(1-866-455-7832)

Bacharach 6300-1004 MGS-150 Gas Transmitter, NO2: 0 - 10 ppm, Standard Housing

Item #:
6300-1004
Brand:
Bacharach
Bacharach 6300-1004 MGS-150 Gas Transmitter, NO2: 0 - 10 ppm, Standard Housing
$734.50
Qty
Send This Page to a Friend

Ask an Expert

Our tech experts are ready to help!

1-866-4 JJSTECH (1-866-455-7832)

Email Us
Share this product:
Bacharach 6300-1004 MGS-150 Gas Transmitter, NO2: 0 - 10 ppm, Standard Housing

Bacharach 6300-1004 MGS-150 Gas Transmitter, NO2: 0 - 10 ppm, Standard Housing

$734.50

6300-1004 MGS-150 Gas Transmitter, NO2: 0 - 10 ppm, Standard Housing by Bacharach

MGS-150 Series Gas Transmitter is a feature-rich gas detection system with a wide range of sensor options to provide real-time monitoring of refrigerant, combustible, and toxic gases. It comes standard with user-selectable analog and digital outputs that can be set for 4-20 mA, 0-5V, 1-5V, 0-10V, or 2-10V; allowing them to connect directly to most BMS, SCADA or control systems. Alarm indicators include an onboard alarm LED and audible buzzer, in addition to an alarm relay for connection to external audible/visual alarms or a BMS system. The product's alarm threshold value is pre-set to factory defaults but is also field programmable. A variety of housing options are available (shown below), from standard IP41 enclosures to IP66 water resistant housings, which allow the MGS-150 Series gas sensors to be placed in the toughest of conditions.

Ideal for Commercial and Industrial Refrigeration, Food Storage and Food Processing Facilities, Supermarkets, Parking Garages, Wastewater Treatment Facilities, Hospitals and Universities.

Features & Benefits:

  • Infrared, semiconductor and electrochemical sensor options to meet almost any gas detection need - at the most affordable cost.
  • User-selectable analog outputs: 4-20 mA, 0-5V, 0-10V, 1-5V, 2-10V featuring 12/24 VAC/VDC operation.
  • Fast-response sensors detect leaks quickly, which protect personnel and minimize refrigerant gas usage and environmental impact.
  • Long-life semiconductor sensors for detection of all refrigerants, ammonia, halocarbons, combustible gases & VOCs.
  • Robust design and remote sensor options allow units to be placed directly in areas where detection is needed.
  • Available in a variety of housings, including IP66 and duct mount, for placement in the toughest of environments.
Technical Specifications:
Power Supply 12/24 VAC/VDC operation
Power Consumption (12V) NDIR: 140 mA • SC: 160 mA • EC: 60 mA
Power Monitoring Green LED
Visual Alarm Red LED
Audible Alarm Buzzer, enabled/disabled
Fault Monitoring Red LED (On) • Green LED (Off)
Fault States 0-1 V / 0-2 mA outputs
Analog Outputs 4-20 mA, 0-5 V, 0-10 V, 1-5 V, 2-10 V
Relay Output (Volt-free) 1 relay, 1 amp 24 VAC/VDC
Alarm Delay Selectable: 0, 1, 5 or 10 minutes
IP Rating IP41 (standard) • IP66 (optional)
Dimensions & Weight - enclosures types Standard IP41: 3.35"x5.59"x2.09", 6.3oz. (86 x 142 x 53mm, 180g)
IP66: 6.89"x6.5"x3.29", 1lb. 6oz. (175 x 165 x 82mm, 629g)
IP66 w/Splash: 6.89"x8.9"x3.29", 1lb. 8.7oz. (175 x 225 x 82mm, 700g)
IP66 / Remote: 6.89"x6.1"x3.29", 1lb. 11oz. (175 x 155 x 82mm, 790g)
IP66 / EXd: 6.89"x6.1"x3.29", 2lb. 10oz. (175 x 155 x 82mm, 1185g)
PRV / IP66: 6.89"x6.1"x3.29", 2lb. 0.3oz. (175 x 155 x 82mm, 916g)
Airflow / Duct: 6.89"x4.9"x3.29", 1lb. 4oz. (175 x 125 x 82mm, 578g)
EXd ATEX only): 5.12"x6.3"x3.54", 9lb. 4oz. (130 x 160 x 90mm, 4200g)
Approvals CE • IEC 61010 (pending) • EXd • UL CSA (pending)

Sensor Specifications:
  Infrared (NDIR) Semiconductor (SC) Electrochemical (EC)
Temperature Range -4° F to 122° F (Stand. housing)
-20° C to 50° C (Stand. housing)
-40° F to 122° F (IP66 housing)
-40° C to 50° C (IP66 housing)
-4° F to 122° F (Stand. housing)
-20° C to 50° C (Stand. housing)
-40° F to 122° F (IP66 housing)
-40° C to 50° C (IP66 housing)
-4° F to 122° F (Stand. housing)
-20° C to 50° C (Stand. housing)
-40° F to 122° F (IP66 housing)
-40° C to 50° C (IP66 housing)
Humidity (non-condensing) 0 - 95% 0 - 95% 0 - 95%
Sensor Life 8 years, typical 5 - 8 years, typical 2 - 5 years, typical
Time to Alarm (T50) 25 seconds, typical 20 seconds, typical 80 seconds, typical
Time to Alarm (T90) 90 seconds, typical 50 seconds, typical 220 seconds, typical
Recovery Time 210 seconds, typical 900 seconds, typical 600 seconds, typical
Infrared (NDIR) Sensor Gas(es) Detected Measuring Range(s)
  Carbon Dioxide (CO2) 0 - 1,000 ppm
0 - 2,000 ppm
0 - 5,000 ppm
O - 10,000 ppm (0-1% vol.)
0 - 20,000 ppm (0-2% vol.)
0 - 5%, 0 - 10%
Hydrocarbons (Methane, propane, etc.) 0 - 100% LEL, 0 - 100% vol.
Semiconductor Sensor Gas(es) Detected Measuring Range(s)
  Refrigerants - HFCs: (R134a, R404a, R407, R410a, & many more) 0 - 1,000 ppm
Refrigerants - HFCs: (R22 & more) 0 - 1,000 ppm
Refrigerants - CFCs (R11, R12 & more) 0 - 1,000 ppm
Ammonia (NH3) 0 - 10,000 ppm
Hydrogen (H2) 0 - 2,000 ppm
Hydrocarbons: Methane (natural gas), Propane, Butane, LPG, Ethylene, Isobutane 0 - 2,000 ppm
VOCs: Acetone, Ethanol, Methanol, Trichloro-ethylene and more 0 - 2,000 ppm
Electrochemical Sensor Gas(es) Detected Measuring Range(s)
  Ammonia (NH3) 0 - 100 ppm • 0 - 500 ppm • 0 - 1,000 ppm • 0 - 5,000 ppm
Carbon Monoxide (CO) 0 - 100 ppm • 0 - 500 ppm • 0 - 1,000 ppm
Chlorine (Cl2) 0 - 20 ppm
Chlorine Dioxide (ClO2) 0 - 1 ppm
Ethylene Oxide (C2H4O) 0 - 20 ppm
Ethylene (C2H4) 0 - 20 ppm • 0 - 1,000 ppm
Fluorine (F2) 0 - 1 ppm
Hydrazine (N2H2) 0 - 1 ppm
Saline - Hydride (SiH4) 0 - 5 ppm
Hydrogen (H2) 0 - 1,000 ppm
Hydrogen Chloride (HCl) 0 - 50 ppm
Hydrogen Cyanide (HCN) 0 - 50 ppm
Hydrogen Sulfide (H2S) 0 - 30 ppm • 0 - 200 ppm
Nitric Oxide (NO) 0 - 100 ppm • 0 - 1,000 ppm
Nitrogen Dioxide (NO2) 0 - 10 ppm
Oxygen (O2) 0 - 30% vol.
Ozone (O3) 0 - 2 ppm
Phosgene (COCl2) 0 - 1 ppm
Phosphine (PH3) 0 - 5 ppm
Sulfur Dioxide (SO2) 0 - 100 ppm

Questions & Answers