Bacharach's MGD-100 Series is a robust and scalable gas detection system used for reliable real-time monitoring of refrigerant, combustible, and toxic gases. It's a stand-alone system that alarms when pre-set thresholds are exceeded. The MGD-100's alarms are monitored by a centralized controller, which can alert personnel of potential hazardous conditions via an onboard buzzer and LED alarm indicators.

MGD-100 Systems can be configured from single-sensor, one-alarm level systems to larger scale systems consisting of 6 sensors with 2 alarm levels. This flexibility allows the platform to be used for both small and large systems.

Ideal for Chiller Rooms, Supermarkets, Brewing and Bottling Facilities, Industrial Refrigeration, Arenas, Food Storage and Processing Facilities.

Features & Benefits:

  • Stand-alone, out-of-the-box solution with quick and easy installation - the most cost-effective system available.
  • Fast-response sensors detect leaks quickly, which minimize refrigerant gas usage and environmental impact.
  • Infrared (NDIR) CO2 detection
  • Long-life semiconductor sensors for detection of all refrigerants, ammonia, halocarbons, combustibles & VOCs
  • Robust design allows units to be placed directly in areas where detection is needed.
  • Available in a variety of housings, including IP66 and duct mount.
  • Select from 1, 2, 4 or 6 remote sensors and 1 or 2 pre-set alarm levels, which can be connected to BMS systems.
Technical Specifications:
  Controller with 1 or 2 Sensors Controller with 4 or 6 Sensors
Power Supply Available in 110VAC 60Hz • 12VDC • 220VAC 50Hz
Alarm Levels One Level Two Levels One Level Two Levels
Power Monitoring Green LED Green LED Green LED Green LED
Visual Alarm Red LED Red LED Red LED Red LED
Fault Monitoring Red LED, relay, siren inactive Red LED, relay, siren inactive Red LED, relay, siren inactive Red LED, relay, siren inactive, fault relay active
Audible Alarm Internal buzzer continuous Internal buzzer intermittent (low), continuous (high) External buzzer continuous External buzzer continuous
Buzzer Deactivate By onboard jumper By key switch By onboard jumper By key switch
Alarm Relay
(Volt-free)
10 amp@ 120v or 230v 10 amp@ 120v or 230v (both low & high level) 10 amp@ 120v or 230v 10 amp@ 120v or 230v (both low & high level)
Relay Expander Box
(one relay for each sensor/alarm level)
N/A N/A N/A Available
Alarm Reset Automatic when gas clears Automatic when gas clears (low), Latch out, manual reset by push button when gas clears (high) Automatic when gas clears Automatic when gas clears (low), Latch out, manual reset by push button when gas clears (high)
Delayed Response Selectable (3 mins. when on) 25 seconds (low)
30 seconds (high)
Selectable (3 mins. when on) 25 seconds (low)
30 seconds (high)
Power-On Delay 3 minutes to stabilize from power-up; slightly longer from storage.
Ratings Controller: IP51 Standard Sensor: IP41 Controller: IP51 Standard Sensor: IP41
Cabling, Controller-to-Sensor 4 wire shielded cable, 200 feet (61 m) max, 22AWG @ 120VAC • 0.2mm 4 wire shielded cable, 500 feet (152 m) max, 22AWG @ 120VAC • 0.2mm
Dimensions & Weight Standard Controller:
8.4” x 4.1” x 3.15”
214 x 105 x 80 mm
2.9 lbs. / 1.3 kg

Sensor:
3.4” x 4.73” x 2.08”
86 x 120 x 53 mm
0.33 lbs. / 150 g
Standard Controller:
10.3” x 10.4” x 3.3”
262 x 265 x 84 mm
5.7 lbs. / 2.6 kg

Sensor:
3.4” x 4.73” x 2.08”
86 x 120 x 53 mm
0.33 lbs. / 150 g
Dimensions & Weight - other enclosures Standard: 3.35”x5.59”x2.09” / 6.3oz. • 86 x 142 x 53mm / 180g
IP66: 6.89”x6.5”x3.29” / 1lb. 6oz. • 175 x 165 x 82mm / 629g
IP66 w/Splash: 6.89”x8.9”x3.29” / 1lb. 8.7oz. • 175 x 225 x 82mm / 700g
IP66 w/Remote: 6.89”x6.1”x3.29” / 1lb. 11oz. • 175 x 155 x 82mm / 790g
IP66 w/EXd: 6.89”x6.1”x3.29” / 2lb. 10oz. • 175 x 155 x 82mm / 1185g
PRV / IP66: 6.89”x6.1”x3.29” / 2lb. 0.3oz. • 175 x 155 x 82mm / 916g
Airflow/Duct: 6.89”x4.9”x3.29” / 1lb. 4oz. • 175 x 125 x 82mm / 578g
EXd: 5.12”x6.3”x3.54” / 9lb. 4oz. • 130 x 160 x 90mm / 4200g
Approvals CE • UL 61010-1 (pending) • CAN/CSA 22.2 61010-1 (pending)

Sensor Specifications:
  Infrared (NDIR) Sensor Semiconductor Sensor
Temperature Range -4° F to 122° F (Standard housing)
-20° C to 50° C (Standard housing)
-40° F to 122° F (IP66 housing)
-40° C to 50° C (IP66 housing)
-4° F to 122° F (Standard housing)
-20° C to 50° C (Standard housing)
-40° F to 122° F (IP66 housing)
-40° C to 50° C (IP66 housing)
Humidity (non-condensing) 0 - 95% 0 - 95%
Sensor Life 5 years, typical 5 - 8 years, typical
Time to Alarm 30 seconds, typical 24 seconds, typical
Recovery Time 210 seconds, typical 600 seconds, typical
Infrared (NDIR) Sensor Gas(es) Detected Programmed Detection Range
  Carbon Dioxide (CO2) 0 - 5,000 ppm
0 - 10,000 ppm
0 - 20,000 ppm
0 - 30,000 ppm
0 - 50,000 ppm
0 - 1% vol
Hydrocarbons (Combustibles) 0 - 100% LEL, 0 - 100% vol
Semiconductor Sensor Gas(es) Detected Programmed Detection Range
  Refrigerants, HFC, CFCs, HCFCs: including R134a, R404a, R407a, R410a, R507a, R11, R12, R22, R600a, R290 and many more 1,000 ppm*
Ammonia (NH3) 500 ppm - 1,000 ppm*
Hydrogen (H2) 0 - 2,000 ppm*
Hydrocarbons:
Ethylene, methane and more
0 - 2,000 ppm*
VOCs:
including Acetone, Methanol,
Trichloroethylene and more
0 - 2,000 ppm*